Disconnecting / turning off heat strips
How to quickly disable heat strips in your wall unit if you don’t need them or need to hit a lower power ceiling
Coming soon…
But you can still contact us to walk you through it!
Installing a heat strip kit
We walk you through installing, configuring, and testing your wall unit’s heat strip kit
Wall mount electrical requirements
Quickly check the minimum breaker size required to service your Marvair Wall Mount.
Note: This data is based on Smart Builder configurations. For the full table, download the Product Data Sheets.
AC 208/230V 1ph | 2-ton | 3-ton | 4-ton | 5-ton |
---|---|---|---|---|
Base | 35A | 40A | 50A | 60A |
10kW Kit | 60A | 60A | 60A | 60A |
15kW Kit | N/A | 90A | 90A | 90A |
HP 208/230V 1ph | 2-ton | 3-ton | 4-ton | 5-ton |
---|---|---|---|---|
Base | 50A | 60A | 60A | 80A |
10kW Kit | 80A | 90A | 90A | 100A |
15kW Kit | N/A | 110A | 125A | 125A |